01 / Construction & ratings

Construction & ratings

  • IEC 60228 Conductors of insulate cables
  • NFC 33-226 Câbles isolés et leurs accessoires pour réseaux d’énergie Câbles de tensions assignées comprises entre 6/10(12) kV et 18/30(36) kV, isolés au polyéthylène réticulé à gradient fixé, pour réseaux de distribution
  • IEC 60502-2 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 30kV(Um=36kV) – Part 2:Cables for rated voltages of 6kV(Um=7.2kV) and 30kV(Um=36kV)
  • Conductor: Aluminum, class 2,circular compacted conductors
  • Conductor screen: Non-metallic,semi-conducting compound
  • Insulation:Cross-linked polyethylene(XLPE)
  • Insulation screen:Non-metallic,semi-conducting compound,extruded strippable grooved elastomer
  • Longitudinal water tightness(Optional): Swelling powder
  • Metallic screen: Aluminium plastic tape (AL/PET)or Copper tape
  • Outer sheath: Polyethylene (PE)
  • Messenger conductor: Stranded galvanized steel wires
  • Messenger insulation(Optional): Polyethylene (PE)

02 / Technical data

Technical data

Product identifiers, units and manufacturer specification data are kept in their original form.

Medium Voltage Aerial Bundled Cable · 01
No.of cores and nominal cross sectionPhase coreMessengerApprox. overall diameterApprox. weightMax.DC resistance of conductor at 20℃
Min.Number of wiresNominal insulation thicknessNominal AL/PET tape thicknessNominal sheath thicknessConductorNominal insulation thickness
mm²No.mmmmmmNo./mmmmmmkg/kmΩ/km
6/10(12)kV
3×1×50+1×5063.40.227/3.01.249.919480.641
3×1×70+1×50123.40.227/3.01.253.622390.443
3×1×95+1×50153.40.227/3.01.257.525790.32
3×1×120+1×50153.40.227/3.01.26028590.253
3×1×150+1×50153.40.227/3.01.263.331820.206
3×1×185+1×50303.40.227/3.01.26735990.164
3×1×240+1×50303.40.227/3.01.271.942330.125
3×1×300+1×50303.40.227/3.01.276.748890.100
3×1×400+1×50533.40.22.27/3.01.283.458520.0778
3×1×500+1×50533.40.22.27/3.01.290.969910.0605
3×1×630+1×50533.40.22.47/3.01.299.885050.0469
8.7/16(17.5)kV
3×1×50+1×5064.50.227/3.01.255.122200.641
3×1×70+1×50124.50.227/3.01.258.825280.443
3×1×95+1×50154.50.227/3.01.262.628880.32
3×1×120+1×50154.50.227/3.01.265.231810.253
3×1×150+1×50154.50.227/3.01.268.535200.206
3×1×185+1×50304.50.227/3.01.272.139560.164
3×1×240+1×50304.50.22.17/3.01.277.546480.125
3×1×300+1×50304.50.22.17/3.01.282.353290.100
3×1×400+1×50534.50.22.27/3.01.288.662920.0778
3×1×500+1×50534.50.22.37/3.01.296.675090.0605
3×1×630+1×50534.50.22.47/3.01.210590270.0469
12/20(24)kV
3×1×50+1×5065.50.227/3.01.259.824900.641
3×1×70+1×50125.50.227/3.01.263.528160.443
3×1×95+1×50155.50.227/3.01.267.431930.32
3×1×120+1×50155.50.227/3.01.27034990.253
3×1×150+1×50155.50.227/3.01.273.238530.206
3×1×185+1×50305.50.227/3.01.276.943060.164
3×1×240+1×50305.50.22.17/3.01.282.350220.125
3×1×300+1×50305.50.22.27/3.01.287.557630.1
3×1×400+1×50535.50.22.37/3.01.293.767560.0778
3×1×500+1×50535.50.22.47/3.01.2101.780140.0605
3×1×630+1×50535.50.22.57/3.01.2110.295740.0469
18/30(36)kV
3×1×50+1×50680.227/3.01.270.631770.641
3×1×70+1×501280.227/3.01.274.335400.443
3×1×95+1×501580.22.17/3.01.278.639910.32
3×1×120+1×501580.22.17/3.01.281.243240.253
3×1×150+1×501580.22.27/3.01.284.947480.206
3×1×185+1×503080.22.27/3.01.288.652420.164
3×1×240+1×503080.22.37/3.01.29460180.125
3×1×300+1×503080.22.47/3.01.299.168160.100
3×1×400+1×505380.22.57/3.01.2105.478800.0778
3×1×500+1×505380.22.67/3.01.2113.492240.0605
3×1×630+1×505380.22.77/3.01.2121.8121.80.0469

Before you specify

What information should I include in an inquiry?

Include the product designation, operating voltage, conductor size, number of cores, required length and delivery destination. Add installation conditions and any required standard.

Can I use these tables to make the final cable selection?

Use the published values to compare products. Confirm the final construction, current rating and installation requirements with your project engineer and the supplier.

How can I keep a copy of this specification?

Use Print / Save PDF on this page. The print layout includes the product name, construction details and specification tables.

Can the team review a project specification?

Send your requirements through the inquiry form. Include the relevant drawings or document references in your message so the team can follow up.

Related cables

Contact us

Bring your next connection into focus.

Share your application, working voltage, cable size and destination. Our team can help you identify the next step.

Discuss a project

Tell us what you are planning.

Your details are used to respond to this inquiry. Privacy