Products

19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1)

Review the construction and specification data below to compare this cable with your project requirements.

01 / Construction & ratings

Construction & ratings

  • Conductor – Plain annealed class 2 compacted copper
  • Conductor screen – Semi-conductive compound
  • Insulation – Cross linked polyethylene (XLPE)
  • Insulation screen – Semi-conductive compound
  • Metallic screen – Plain annealed copper wire
  • PP rope filler
  • Binder tape – Non-hygroscopic material tape
  • Separation layer – Polyvinyl chloride compound (PVC 5V-90)
  • Armor – Hard drawn aluminum wires for single core or Galvanized steel wire for multi core
  • Outer sheath – Polyvinyl chloride compound (PVC 5V-90)
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1)

02 / Technical data

Technical data

Product identifiers, units and manufacturer specification data are kept in their original form.

19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 01
Nominal conductor areamm²507095120150185240300400500630
Conductor diametermm8.210.011.613.014.616.218.420.623.426.630.0
Nominal insulation thicknessmm8.08.08.08.08.08.08.08.08.08.08.0
Nominal insulation diametermm26.528.329.931.332.934.536.738.941.744.948.3
Nominal screen area on each coremm²48.768.768.768.768.768.768.768.768.768.768.7
Approx.cable diametermm44.546.548.150.952.754.356.959.362.565.969.7
Approx.weightkg/km25713081340939204300472454236133714483669898
Min. bending radius of duringinstallationmm8709109409901030106011101160122012901360
Min. bending radius of after installationmm580610630660690710740770810860910
Max. pulling tension of conductorkN3.44.86.58.210.212.616.420.427.234.042.9
Max. DC. Resistance of conductor at 20 ℃ohm/km0.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.0283
Max. AC. Resistance of conductor at 90 ℃ohm/km0.3420.2470.1960.1590.1280.0980.07900.06300.05080.04131.4664
Inductance,trefoil,touchingmH/km0.5270.4960.4730.4620.4450.4310.4140.4000.3850.3700.357
Conductor to screen capacitanceμF/km0.1430.1590.1730.1850.1990.2130.2330.2520.2760.3030.332
Min Insulation resistance @20℃Mohm. km15511139221277411921110801035495038784801672906652
Fault current capacity of phase conductorKA/1s7.210.013.617.221.526.534.342.957.271.590.1
Fault current capacity of metallic screenKA/1s7.210.210.210.210.210.210.210.210.210.210.2
current rating – Ground,direct buriedA205250295335370420480535605675750
current rating – In free air unclose spaceA220275330380430490570655750855970
current rating – In ground single way ductA200230275310340375425470520575630
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 02
Nominal conductor areamm²507095120150185240300400
Conductor diametermm8.210.011.613.014.616.218.420.623.4
Nominal insulation thicknessmm8.08.08.08.08.08.08.08.08.0
Nominal insulation diametermm26.528.329.931.332.934.536.738.941.7
Nominal screen area on each coremm²49.468.168.168.168.168.168.168.168.1
Approx.cable diametermm86.090.394.097.4101.3105.1110.3115.6122.3
Approx.weightkg/km105311195213205144181584417418198482239825862
Min. bending radius of duringinstallationmm168017601830190019702050215022502380
Min. bending radius of after installationmm112011801220127013201370143015001590
Max. pulling tension of conductorkN10.214.319.424.530.637.749.061.281.6
Max. DC. Resistance of conductor at 20 ℃ohm/km0.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. AC. Resistance of conductor at 90 ℃ohm/km0.3420.2460.1960.1590.1270.0970.07780.06150.0487
Inductance,trefoil,touchingmH/km0.4540.4260.4050.3910.3760.3640.3490.3370.324
Conductor to screen capacitanceμF/km0.1430.1590.1730.1850.1990.2130.2330.2520.276
Min Insulation resistance @20℃Mohm. km155111392212774119211108010354950387848016
Fault current capacity of phase conductorKA/1s7.210.013.617.221.526.534.342.957.2
Fault current capacity of metallic screenKA/1s7.310.110.110.110.110.110.110.110.1
current rating – Ground,direct buriedA205250295340380430495560640
current rating – In free air unclose spaceA215265325375425485575655755
current rating – In ground single way ductA170210255290320365420475560
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 03
Temp.(℃)20253540455055
Rating factor1.181.141.0510.950.890.84
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 04
Temp.(℃)10152025303540
Rating factor1.111.071.0410.960.920.88
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 05
Depth of burial (m)Rating factor up to 300mm²Rating factor above 300mm²Rating factor above 300 mm² single coreRating factor above 300 mm² three core
0.801.001.001.001.00
1.000.980.970.980.99
1.250.960.950.950.97
1.500.950.930.940.96
1.750.940.910.920.96
2.000.920.890.910.95
2.500.910.880.890.94
3.000.900.860.880.93
19/33(36)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 06
Nominal area of conductor (mm²)Thermal resistivity (℃.m/W)0.80.91.01.21.52.02.53.0
Single coreRating factors
up to 1501.161.111.071.000.910.810.730.67
180 to 4001.171.121.081.000.900.800.720.66
above 4001.181.131.081.000.900.790.710.65
Three-coreRating factors
up to 161.091.061.041.000.950.870.790.74
25 to 1501.141.101.071.000.930.840.760.70
185 to 4001.161.111.071.000.920.820.740.68

Before you specify

What information should I include in an inquiry?

Include the product designation, operating voltage, conductor size, number of cores, required length and delivery destination. Add installation conditions and any required standard.

Can I use these tables to make the final cable selection?

Use the published values to compare products. Confirm the final construction, current rating and installation requirements with your project engineer and the supplier.

How can I keep a copy of this specification?

Use Print / Save PDF on this page. The print layout includes the product name, construction details and specification tables.

Can the team review a project specification?

Send your requirements through the inquiry form. Include the relevant drawings or document references in your message so the team can follow up.

Related cables

Contact us

Bring your next connection into focus.

Share your application, working voltage, cable size and destination. Our team can help you identify the next step.

Discuss a project

Tell us what you are planning.

Your details are used to respond to this inquiry. Privacy