Products

12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1)

Review the construction and specification data below to compare this cable with your project requirements.

01 / Construction & ratings

Construction & ratings

  • Conductor – Plain annealed class 2 compacted copper
  • Conductor screen – Semi-conductive compound
  • Insulation – Cross linked polyethylene (XLPE)
  • Insulation screen – Semi-conductive compound
  • Metallic screen – Plain annealed copper wire
  • PP rope filler
  • Binder tape – Non-hygroscopic material tape
  • Separation layer – Polyvinyl chloride compound (PVC 5V-90)
  • Armor – Hard drawn aluminum wires for single core or Galvanized steel wire for multi core
  • Outer sheath – Polyvinyl chloride compound (PVC 5V-90)
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1)

02 / Technical data

Technical data

Product identifiers, units and manufacturer specification data are kept in their original form.

12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 01
Nominal conductor areamm²35507095120150185240300400500630
Conductor diametermm7.08.210.011.613.014.616.218.420.623.426.630.0
Nominal insulation thicknessmm5.55.55.55.55.55.55.55.55.55.55.55.5
Nominal insulation diametermm19.720.922.724.325.727.328.931.133.336.139.342.7
Nominal screen area on each coremm²34.448.768.768.768.768.768.768.768.768.768.768.7
Approx.cable diametermm36.338.540.342.143.545.346.950.552.956.159.563.3
Approx.weightkg/km175121562628296932593611401848365522649976729178
Min. bending radius of duringinstallationmm7107507908208508909209901030110011601240
Min. bending radius of after installationmm480500530550570590610660690730780830
Max. pulling tension of conductorkN2.43.44.86.58.210.212.616.420.427.234.042.9
Max. DC. Resistance of conductor at 20 ℃ohm/km0.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.0283
Max. AC. Resistance of conductor at 90 ℃ohm/km0.6680.4940.3420.2470.1960.1590.1280.09830.07940.06360.05150.0422
Inductance,trefoil,touchingmH/km0.5180.4980.4670.4460.4300.4150.4010.3910.3770.3640.3500.338
Conductor to screen capacitanceμF/km0.1630.1790.2020.2220.2400.2600.2800.3080.3350.3700.4100.452
Min Insulation resistance @20℃Mohm. km135661238210962995692198504789371866597597553964892
Fault current capacity of phase conductorKA/1s5.07.210.013.617.221.526.534.342.957.271.590.1
Fault current capacity of metallic screenKA/1s5.17.210.210.210.210.210.210.210.210.210.210.2
current rating – Ground,direct buriedA175205250295335370415480535600670740
current rating – In free air unclose spaceA185220270330375425485565645740845960
current rating – In ground single way ductA170195235275305335370415460510560615
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 02
Nominal conductor areamm²35507095120150185240300400
Conductor diametermm7.08.210.011.613.014.616.218.420.623.4
Nominal insulation thicknessmm5.55.55.55.55.55.55.55.55.55.5
Nominal insulation diametermm19.720.922.724.325.727.328.931.133.336.1
Nominal screen area on each coremm²34.049.468.168.168.168.168.168.168.168.1
Approx.cable diametermm67.870.875.379.083.787.591.496.5101.9108.5
Approx.weightkg/km6682750688219972120291331214876172031958622915
Min. bending radius of duringinstallationmm1320138014701540163017101780188019902110
Min. bending radius of after installationmm8809209801030109011401190126013301410
Max. pulling tension of conductorkN7.110.214.319.424.530.637.749.061.281.6
Max. DC. Resistance of conductor at 20 ℃ohm/km0.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470
Max. AC. Resistance of conductor at 90 ℃ohm/km0.4940.3420.2460.1960.1590.1270.0970.07790.06150.0487
Inductance,trefoil,touchingmH/km0.4340.4120.3870.3680.3550.3420.3320.3190.3080.297
Conductor to screen capacitanceμF/km0.1630.1790.2020.2220.2400.2600.2800.3080.3350.370
Min Insulation resistance @20℃Mohm. km1356612382109629956921985047893718665975975
Fault current capacity of phase conductorKA/1s5.07.210.013.617.221.526.534.342.957.2
Fault current capacity of metallic screenKA/1s5.07.310.110.110.110.110.110.110.110.1
current rating – Ground,direct buriedA170200240290330365410475530638
current rating – In free air unclose spaceA170200250305350390445520590754
current rating – In ground single way ductA145170210245285320360415470539
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 03
Temp.(℃)20253540455055
Rating factor1.181.141.0510.950.890.84
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 04
Temp.(℃)10152025303540
Rating factor1.111.071.0410.960.920.88
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 05
Depth of burial (m)Rating factor up to 300mm²Rating factor above 300mm²Rating factor above 300 mm² single coreRating factor above 300 mm² three core
0.801.001.001.001.00
1.000.980.970.980.99
1.250.960.950.950.97
1.500.950.930.940.96
1.750.940.910.920.96
2.000.920.890.910.95
2.500.910.880.890.94
3.000.900.860.880.93
12.7/22(24)kV XLPE Insulated Single Core and 3Cores Power Cable (AS/NZS 1429.1) · 06
Nominal area of conductor (mm²)Thermal resistivity (℃.m/W)0.80.91.01.21.52.02.53.0
Single coreRating factors
up to 1501.161.111.071.000.910.810.730.67
180 to 4001.171.121.081.000.900.800.720.66
above 4001.181.131.081.000.900.790.710.65
Three-coreRating factors
up to 161.091.061.041.000.950.870.790.74
25 to 1501.141.101.071.000.930.840.760.70
185 to 4001.161.111.071.000.920.820.740.68

Before you specify

What information should I include in an inquiry?

Include the product designation, operating voltage, conductor size, number of cores, required length and delivery destination. Add installation conditions and any required standard.

Can I use these tables to make the final cable selection?

Use the published values to compare products. Confirm the final construction, current rating and installation requirements with your project engineer and the supplier.

How can I keep a copy of this specification?

Use Print / Save PDF on this page. The print layout includes the product name, construction details and specification tables.

Can the team review a project specification?

Send your requirements through the inquiry form. Include the relevant drawings or document references in your message so the team can follow up.

Related cables

Contact us

Bring your next connection into focus.

Share your application, working voltage, cable size and destination. Our team can help you identify the next step.

Discuss a project

Tell us what you are planning.

Your details are used to respond to this inquiry. Privacy